Description
Mitreh CS0032 solution not only raises the boiling temperature and lowers the freezing temperature, also it prevents foam formation, scale formation and clogging of the ducts and installations, as well as their corrosion, especially during system overhaul. As a result, once the system is restarted, there are no previous problems, such as clogging and bursting of pipes, and the service useful life of the system and installations increases. The solution contains compounds which inject into the water in the installations, prevents freezing of water at low temperatures and greatly increase the boiling temperature of the water, while preventing scale formation and corrosion control, Increases the useful life of the installations.
Calibration of Using Mitreh CS0032 Solution:
According to the calibration table, the required amount of solution is injected into the system depends on the type of use. This solution provides thermal equilibrium throughout the system after being combined with water at the same time as heat dissipation is produced. Simply put, it prevents freezing or boiling water in the cold and warm seasons of the year. On the other hand, there are compounds in this solution that prevent the rusting of installations and the formation of scale caused by solutes in water.
Range | Row | Type of use | Product code | Temperature range | Consumption |
For Cryogenic Range | 1 | cryogenic industry installations | CS0032 | 0 to 15 | One liter for every 2-3 liters of water |
2 | 23- to -15 | One liter for every 1-2 liters of water | |||
3 | 34- to 23- | One liter per liter of water | |||
4 | 48- to 34- | One liter for every 0.5-1 liter of water | |||
For Thermal Range | 1 | Thermal industry installations | CS0032
| Up to 110 ˚C | One liter per 500ml of water |
2 | Up to 124 ˚C | One liter per 250ml of water | |||
3 | Up to 140 ˚C | One liter per 100ml of water | |||
4 | Up to 197 ˚C | Pure solution | |||
Ø The above calculations are for use with tap water. If you use harder water, contact your nearest Abrizan company technical office in your area. Ø Before injecting CS solution into the system, make sure that the installation is free of scale and environmental contaminants and rinse the system with cold, industrial Mitreh solutions if any scales are present.
|
Some Physical Properties of the Solution:
Property | Property | ||
Liquid | Physical state | 6.1 – 6.8 | pH |
Green | Color | 106 – 110 | Boiling temperature range (˚C), 50% solution |
Odorless | Odor | -37 – -45 | Freezing temperature range (˚C), 50% solution |
1.071 – 1.079 | Density at 20˚C (gr⁄ml) | dissolves rapidly | Solubility in water |
Reviews